5930-00-004-7701 SWITCH,PUSH Index 5950-00-004-7704 TRANSFORMER,POWER

National Stock Number:
5925-00-004-7703

Federal Supply Class:
5925

National Item Identification Number:
000047703

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
TE111010WL60969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL
W-C-375/1081348FEDERAL SPECIFICATIONS PROMULGATED BY GENERAL SERVICES ADMINISTRATION WASHINGTON DC
WC375/10-00181348FEDERAL SPECIFICATIONS PROMULGATED BY GENERAL SERVICES ADMINISTRATION WASHINGTON DC


Techincal Specification:
POLE QUANTITY1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE10.0 AMPERES AC SINGLE LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
TERMINAL TYPE AND QUANTITY2 COMPRESSION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC SINGLE LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND
TIME DELAY SINGLE LOCATION
RESET METHODMANUAL
BODY STYLESINGLE POLE TYPE
MOUNTING FACILITY TYPE AND QUANTITY4 SLOT
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL-MAGNETIC SINGLE LOCATION
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS7500.0 AC SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING40.0 DEG CELSIUS NOMINAL SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH6.310 INCHES NOMINAL
BODY WIDTH1.370 INCHES MINIMUM AND
1.380 INCHES MAXIMUM
BODY HEIGHT3.380 INCHES NOMINAL
BOSS HEIGHT0.250 INCHES NOMINAL
MOUNTING SLOT WIDTH0.375 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDCORROSION RESISTANT
TEST DATA DOCUMENT81348-W-C-375 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
FRAGILITY FACTORMODERATELY RUGGED
SPECIFICATION/STANDARD DATA81348-W-C-375/10 GOVERNMENT SPECIFICATION
SPEC/STD CONTROLLING DATA
MANUFACTURERS CODE81348
NON-DEFINITIVE GOVERNMENT SPEC/STD REFERENCEW-C-375/10
DEFINITIVE GOVERNMENT SPEC/STD REFERENCEWC375/10-001


Click here to Register for Free 30-day Trial