| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BODY LENGTH | 3.719 INCHES NOMINAL |
| BODY STYLE | SINGLE POLE TYPE |
| BODY WIDTH | 0.990 INCHES NOMINAL |
| BOSS HEIGHT | 0.165 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.063 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 32.0 DC SINGLE LOCATION |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 DC SINGLE LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 80.0 AMPERES DC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.239 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| POLE QUANTITY | 1 |
| RESET METHOD | MANUAL |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 80.000 MINIMUM AT 125 PCT AND 200.000 MAXIMUM AT 125 PCT AND 15.000 MINIMUM AT 200 PCT AND 49.000 MAXIMUM AT 200 PCT AND 5.000 MINIMUM AT 300 PCT AND 16.000 MAXIMUM AT 300 PCT SINGLE LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 120.0 SINGLE LOCATION |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| THREAD QUANTITY PER INCH | 32 |