| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +600.0 TO 1300.0 AC ALL LOCATIONS |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| OVERALL HEIGHT | 4.125 INCHES NOMINAL |
| OVERALL LENGTH | 6.500 INCHES NOMINAL |
| OVERALL WIDTH | 4.875 INCHES NOMINAL |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC AND 100.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC AND 10000.0 DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S) |
| NOMINAL THREAD SIZE | 0.190 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC AND 250.0 DC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| PRECIOUS MATERIAL AND LOCATION | MAIN CONTACTS SILVER |
| PRECIOUS MATERIAL | SILVER |
| RESET METHOD | MANUAL |
| SPECIAL FEATURES | ENT2732 IS A FACTORY INSTALLED SHUNT TRIP UNIT WITH AUXILIARY SWITCH; RATED VOLTAGE 120 VDC; RATED CURRENT 100 AMPS |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
| THREAD QUANTITY PER INCH | 32 |
| THREAD SERIES DESIGNATOR | UNF |
| TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |