5935-01-045-9601 SOCKET,PLUG-IN ELECTRONIC COMPON Index 5331-01-045-9603 O-RING

National Stock Number:
5925-01-045-9602

Federal Supply Class:
5925

National Item Identification Number:
010459602

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
Q0-340 50 DEGREE88434SQUARE D CO
QO340 50 DEGREE56303SCHNEIDER ELECTRIC USA, INC.


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESETTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWOAT POLE TWO
BODY HEIGHT2.580 INCHES NOMINAL2.580 INCHES NOMINAL
BODY LENGTH3.000 INCHES NOMINAL3.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH2.090 INCHES NOMINAL2.090 INCHES NOMINAL
BOSS HEIGHT0.250 INCHES NOMINAL0.250 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.740 INCHES NOMINAL0.740 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS60.0 ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONSSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS240.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE1 TOGGLE
MATERIALPLASTIC CASEPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE40.0 AMPERES AC ALL LOCATIONS40.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC ALL LOCATIONS5000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 TERMINAL6 TERMINAL
POLE QUANTITY33
RESET METHODMANUALMANUAL
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT240.000 MAXIMUM AT 200 PCT ALL LOCATIONS240.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONSTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONSMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS125.0 ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 SCREW6 SCREW


Click here to Register for Free 30-day Trial